PT. ETI FIRE SYSTEMS | LISTING DATE & REFERENCE | DESCRIPTION | Submitted 16 January 2009 Listed April 2009 302-0109-005 | Fire Test for ETI engineered fire system. Design reviewed to NFPA 11. Fire Test using 7.5 square meter scenario, protected by 10 nozzle and 35 liters of agent Result : 1. DIRECT EXTINGUISHMENT 8 SECONDS 2. INDERECT EXTINGUISHMENT 48 SECONDS All components listed as defined in Technical Manual 5 | Submitted 16 Jan 2009 Listed April 2009 302-0109-006 | Verification of cylinder vessel design requirements. Design compliance to AS 2470-2005 | March 2010 302-0310-001 | The ETI Engineered Fire Suppression System as defined in the sixth edition Technical Manual listed here in as compliant to AS 5062 - As an Engineered Foam Fire Suppression System |
|