PT. ETI FIRE SYSTEMS

LISTING DATE & REFERENCE

DESCRIPTION

15 Dec 2007

ISB 07-01

Design procedures for the ETI Engineered Foam Water Spray Fire Suppression System. Document ETI Design Manual – fourth edition published October 2007. Compliance to Australian Standard AS 5062 – 2006.

Classification :

  • Pre- Engineered system - NO
  • Engineered System - YES

15 Dec 2007

ISB 07-02

  1. Fire Fighting Performance of the ETI Engineered Foam Water Spray Fire Suppression System. Compliance to Australian Standard AS 5062 – 2006.
  2. Test- Direct fire test – result sixteen (16) seconds to extinguishment.
  3. Test- Indirect fire test – result fourty eight (48) seconds to extinguishment

15 Dec 2007

ISB 07-03

Fire Fighting Performance of the ETI Engineered Foam Water Spray Fire Suppression System to substantial simulated test. Exceeds test to Australian Standard AS 5062 – 2006.
Fire Scenario, large engine simulated environment with indirect sump risk. Use of 12 nozzles, 35 litres foam. Direct extinguishment 10 seconds. Indirect extinguishment 35 seconds.
23 Mar 2008

Design procedures for the ETI Engineered design program. Document Version 10 on excel format. Produces design outcomes consistent with– ETI Design Manual – fourth edition published October 2007 for Compliance to Australian Standard AS 5062 – 2006.

Classification :

  • Pre- Engineered system – NO
  • Engineered System - YES

19 Nov 2008

ISB 08 -01

Design procedures for the ETI Engineered Foam Fire Suppression System. Document ETI Design Manual – fifth edition prepared October 2008 . Compliance to Australian Standard AS 5062 – 2006 and related NFPA11.

DESIGN PROCEDURES, FOAM APPLICATION RATES, COMPONENT COMPLIANCE.

16 Jan 2009

ISB 09 -01

Design program for the ETI Engineered system . Document - Version 11- Microsoft .net format. Contolled download. Produces design outcomes consistent with – ETI Design Manual – fifth edition prepared October 2008 and published January 2009, for Compliance to Australian Standard AS 5062 – 2006.

Classification :

  • Pre-Engineered system – NO
  • Engineered System – YES

16 Jan 2009

ISB 09-02

Fire Test for ETI engineered fire system. Design reviewed to NFPA 11. Fire Test using 7.5 square meter scenario, protected by 10 nozzles and 35 liters of agent

Result :

  1. DIRECT EXTINGUISHMENT 8 SECONDS
  2. INDIRECT EXTINGUISHMENT 48 SECONDS.

16 Jan 2009

ISB 09-03
Verification of cylinder pressure vessel design requirements. Design compliance to AS 2470 – 2005.
 
 